发电厂运行状态(推荐)

时间:2019-05-13 12:35:53下载本文作者:会员上传
简介:写写帮文库小编为你整理了多篇相关的《发电厂运行状态(推荐)》,但愿对你工作学习有帮助,当然你在写写帮文库还可以找到更多《发电厂运行状态(推荐)》。

第一篇:发电厂运行状态(推荐)

一、发电厂电气设备的状态分为运行、热备用、冷备用、检修四种状态。

二、各状态名词解释。

1、运行状态:是指电气设备的隔离开关及断路器都在合闸状态且带有电压。

2、热备用状态:是指电气设备具备送电条件和起动条件,断路器一经合闸就转变为运行状态。电气设备处于热备用状态下,随时有来电的可能性,应视为带电设备。联动备用。

3、冷备用状态:电气设备除断路器在断开位置,隔离开关也在分闸位置。在此状态下,未履行工作许可手续及未布置安全措施,不允许进行电气检修工作,但可以进行机械作业。

4、检修状态:电气值班员按照《电业安全工作规程》及工作票要求布置好安全措施。电气设备的倒闸操作规律就是基于上述四个阶段进行,但检修设备拆除接地线后,应测量绝缘电阻合格,才能转换为另一状态。

第二篇:发电厂运行岗位职责

发电厂运行岗位职责

一、值长:

1、正确执行生产副总经理批准的运行方式。

2、负责全值的安全和经济运行,服从上级调度命令,严格执行有功及无功调度曲线。

3、按照规程要求,全面领导和指挥本值的运行操作和事故处理。

4、担任公司规定的工作票许可人和运行规程中规定的试验主持人。监护值班人员进行重要的操作和事故处理,达到正确无误。

5、领导全值人员发挥安全员、培训员等人员的作用,搞好班组的安全经济运行和人员培训工作。

6、领导全值人员做好清洁卫生工作。

7、负责抓好交接班,开好班前、班后会议。

二、主值

1、全面负责机组各系统的安全文明生产和经济运行工作;值长不在现场时代行值长职权。

2、负责协调安排机组人员各项工作,负责协调机、炉、电、燃料、化学各专业的运行。

3、负责机组的启、停重大操作和操作监护工作。

4、负责机组的异常及事故处理工作,在值长领导监护下,负责指挥运行人员完成事故处理。

5、负责对本机组人员进行技术培训和业务指导及对本机组人员工作质量、劳动纪律等予以考核。

6、直接接受并执行值长的命令,如有疑问须立即并明确提出,如值长坚持,则必须按命令执行;若危害人身和设备安全应拒绝并立即与上级反映。

7、接受值长的具体工作安排和业务指导。对副值及以下岗位运行人员具体工作安排和业务指导。

三、副值:

1、是主值的助手,负责协助主值完成机组安全经济运行;主值不在现场时履行主值职权。

2、协助主值完成机组的监视与调整,指导并协助巡检员完成其操作和巡检工作。

3、配合主值分析、处理机组运行中存在的隐患、异常等不安全因素,调整参数和运行方式,协助主值完成事故处理。

4、接受主值的具体工作安排和业务指导。对巡检员进行具体工作安排和业务指导。

四、巡检员

1、负责就地操作和调整;负责机组设备和系统的巡回检查工作。

2、负责电、机、炉、燃料设备操作巡检和运行维护,负责厂内燃料输送系统的运行。

3、负责工器具管理和文明生产工作。

4、协助副值具体做好各种记录工作。

第三篇:发电厂设备运行分析

发电厂设备运行分析

分析项目:水电站在电力系统中的作用 分析过程:

1、提供电力,作为系统的工作容量分担负荷。可以减少系统火电的系统装机容量;

2、供给系统大量的廉价电量,节省燃料。

3、承担系统备用容量,提高系统供电质量;

4、调节峰荷,改善系统运行条件,降低系统发电成本;

5、起调荷作用,供给无功电力,调节系统电压 总结:

水电站是一个利用水能生产电能的工厂。水能机组是水电站生产能量最重要的动力设备之一。经过水轮发电机将机械能转换为电能。水力发电是目前公认的最清洁的一种能源,同时也是最经济的发电方式。掌握水利机组运行技术对提高水电站乃至电力系统的安全。可靠经济运行水平是十分重要的。因此,水力发电在参与电力系统运行时,它占据一种十分独特的地位,特别是随着电力系统运行时,它占据一种十分独特的地位,特别是随着电力系统容量的扩大,水力发电必将在电力系统中发挥其更大的作用。

一、项目:隔离开关异常运行及事故处理。过程:

隔离开关在运行和操作中,易发生接点和触头过热、合闸不到位等异常情况,电动操作失灵,对此要求运行人员能正确的分析、判断和处理。总结:

1、隔离开关电动操作失灵。首先,检查操作有无差错;然后,检查电流回路是否完好,熔断器是否熔断或松动,电气闭锁回路是否正常

2、隔离开关触头、接点过热,需立即申请调度减小负荷,严重过热时,应立即转移负荷,让后停电处理。

3、隔离开关合闸不到位,多数是挂钩锈蚀、卡涩、检修挑食未调好等原因引起的。发生这种情况,可拉开隔离开关后再次合闸,当电动不到位时,可手动合闸。必要时,应申请停电处理。

4、隔离开关触头熔焊变形,绝缘子破裂和严重放电。遇有上述情况应立即申请停电处理,在停电处理前应加强监视。

二、分析项目:信号系统的分类与区别

信号系统是当运行中电气设备发生故障和存在不正常工作状态时,除要求保护装置做出相相应的反应外,还要求及时告知值班人员引起注意,迅速正确的判断这些故障和不正常工作状态的性质和特点,以便于及时处理。

分析过程:

用来反应故障和不正常工作状态的信号通常由灯光信号和音响信号两部分组成。前者表明故障和正常工作状态的性质和地点,后者用来引起值班人员的注意。按其作用信号分为:

1、位置信号;

2、事故信号

3、预告信号 分析总结:

1、位置信号是用来指示设备运行状态的信号。包括开关的通(断)位置状态,闸门的开、闭位置状态,调节装置调整到极限位置状态和机组所处的状态。

2、事故信号是设备发生故障时,在由继电保护或自动装置使断路器跳闸或机组停机的同时发出的信号。通常使相应的信号灯发光,并同时发出音响信号。为与预告信号相区别,事故信号用蜂鸣器作为发声器具,包括机组过速、低油压、失磁、差动、过流、过压、重瓦斯保护动作等。

3、预告信号是在机组等主要原件及其他设备发生不正常工作状态时所发出的信号。它可以帮助值班人员及时发现不正常工作状态,以便采取适当的措施加以处理,防止故障的扩大。为与事故信号区别,音响预告信号采用警铃作为发声工具。一般有发电机转子一点接地;操作回路断线,冷却水终断等。

三、项目:变压器保护的分析 过程:

变压器保护主要有:

1、差动保护

2、瓦斯保护(重瓦斯、轻瓦斯)

3、复合电压启动过流保护

4、过负荷保护

5、温度升高保护

6、差动断线 总结:

其中属于事故保护的有:

1、差动保护,保护变压器的内部故障及套管电源侧引出线的全部故障

2、重瓦斯保护,防备变压器内部故障及油面过低的主保护

3、负荷电压起动过流保护,保护电网短路故障引起的变压器过流且作为变压器内部及外部短路故障的后备保护。

属于故障保护的有:

1、轻瓦斯保护;动作后发生轻瓦斯动作信号。

2、过负荷保护;防止变压器的电流超过额定值运行的保护,保护动作延时信号。

3、温度升高保护

4、差动断线;差动电流回路、开路。

四、项目:发电机有节奏振荡分析 过程:

控制室看:各种仪表是否剧烈的左右摆动电压低于正常值,听发电机声音是否有节奏的鸣叫;水机房看:各种仪表是否剧烈的左右摆动,电压低于正常值,可控硅励磁装置是否间歇性动作,调速器不能稳定运行有震动现象。听水轮机和发电机是否有撞击声和摩擦声。

总结: 处理方式:(1)查明是系统震荡故障还是机组本身故障引起震荡;(2)汇报领导;(3)和调度联系;

(4)系统故障引起震荡时,听从调度指挥;

(5)是机组本身故障引起震荡时,调整励磁并将机组开度减至空载

(6)震荡故障不能消除时,将机组解列,停机检查。

五、项目:折向器(水轮机内部,不可直接观察)过程:

(1)折向器的气蚀,冲蚀和裂纹检查。(2)折向器的固定螺钉,销子检查。(3)折向器操作杆的销子及销孔检查。(4)折向器操作杆水封的更换。(5)固定折向器的拐臂检查。总结:

折向器的气蚀、冲蚀部位,可在现场进行补焊,焊后进行磨光处理,如有裂纹必须更换。固定螺钉和销子应紧固可靠,无松动现象并有锁定措施。销子和销孔应完好,销子不松动,销子得插销牢固。销孔磨损,孔径变大或椭圆,应镶套后重新配置。更换新水封后,机组在各种工况下运行时不得漏水。拐臂转动轴在运行中不应有向两侧串动的现象,其间隙小于1mm。

六、项目:隔离开关异常运行及事故处理 过程:

在隔离开关的运行和操作中,易发生接点和触头过热电动操作失灵,合闸不到位等一刹那情况。对此,要求运行人员能正确的分析,判断及处理。

总结:

(1)隔离开关电动操作失灵首先检查操作有无差错,然后检查电源回路是否完好熔断器是否熔断或松动,电气闭锁回路是否正常。(2)隔离开关触头,接点过热,需立即申请调度或减小负荷;严重过热时,应转移负荷。然后停电处理。

(3)隔离开关合闸不到位,多数是机构锈蚀、卡涩、检调试为调好等原因引起的。发生这种情况,可拉开隔离开关后再次合闸,当电动不到位时,可手动合闸。必要时,应申请停电处理。

(4)隔离开关触头熔焊变形,绝缘子破裂和严重放电;遇有上述情况应立即申请停电处理,在停电处理前应加强监视。

六、项目:机组轴承甩油量增大的原因分析 处理过程:

机组在正常运行时,机组轴承冷却油应保持一定量得进油量与回油量,形成正常的平衡位置。假如冷却油从轴承甩出,我们就应做进一步分析原因及处理。

总结:

轴承产生甩油的原因:

(1)热油温度过高,油槽上部产生油雾使油面压力增大,油雾便从油槽盖板密封处逸出。

(2)机组在运行时控油管内下侧形成低压与油糟上部之间的压强作用下,油雾沿着主轴与挡油管的环腔向下逸出

总结:将外循环油放大加速油放走,在慢慢根据油面加入冷油。

七、项目:充油式电压互感器的故障处理 过程:

充电式电压互感器有下列故障现象之一者,应立即处理(1)电压互感器高压侧熔断器连续熔断二、三次者;(2)电压互感器发热过高;

(3)电压互感器内部有劈啪声和其他噪声;

(4)电压互感器内部或引出口处有严重喷油、漏油现象

(5)从电压互感器内部发出焦臭即冒烟

(6)线圈与外壳之间或引线与外壳之间有火花放电,互感器本体有单相接地。

总结:

在处理时,如系双母线系统应用母线断路器断开故障电压互感器。如系其他电路中的电压互感器,当用隔里开关切断时,应在隔离开关三相之间或其他电气设备之间有足够的安全距离,以及有一定容量的限流电阻的条件下方能进行。以免在断开隔离开关时产生电弧而造成设备和人身事故。

八、项目:变压器台停送电危险点及其控制措施 过程:

变压器台停送电危险点有:(1)高、低压感应电伤人;(2)物体打击伤人;(3)弧光短路伤人; 总结:

1、感应伤人的控制措施:(1)要严格执行倒闸操作票;

(2)操作应两人进行,一人操作,一人监护,不得站在断路器,隔离开关垂直下方;

(3)应使用合格的绝缘杆,雨天操作应使用有防雨罩的绝缘杆;(4)摘挂跌落式熔断器应使用合格的绝缘棒,其他人员不得触及设备;

(5)应先拉开二次负荷开关再拉开跌开式开关;(6)更换高、低压熔丝必须在地面进行,雷电时严禁进行变压器台更换熔丝工作。

2、物体打击伤人的控制措施:操作人员应戴好安全帽

3、弧光短路伤人的控制措施:

(1)变压器台风大,拉开跌落式开关时,应先拉中相次拉下风相,后拉上风相,合上时先合上风相,次合下风相,后合中相

(2)拉合跌落式开关时,要站好位置,对准方向,用力适中,果断操作。

九、项目:机组轴承温度不正常上升的原因分析 过程:

发电机组在正常运行时,其轴承温度会跟随负荷多少,天气情况,冷却系统等的变化而改变,但其会在一个正常范围内变化,突然改变则要查因。

总结:

机组轴承温度突然不正常上升的原因:(1)冷却水中断或减小,打捞漂浮物;(2)轴承油位低,增大供油量;

(3)轴承冷却器漏油或进水,更换损坏件,更换冷却油;

(4)温度表损坏,更换。

十、项目:发电机突然有节奏的不正常鸣响的判断分析 过程: 判断为震荡的条件:

(1)发电机转子励磁电流下降,定子电流升高;(2)有功功率的指针在摆动;

(3)发电机发出鸣声,其鸣声的变化与仪表指针摆动的频率相对应。

总结:

应尽快增加发电机的励磁电流来创造回复周期的条件,还应适当调低负荷,以帮助尽快回复周期,在无法恢复同步时,只能将发电机与系统解列。

十一、项目:机组过速现象的分析 过程:

机组过速现象有:(1)机组发出超速声;(2)机组重负荷频率升高 总结:

应关小导水叶开度,11%为一级过速,保护装置动作发信号,14%为二级过速,保护动作关闭机组,值班员应设法关闭导水叶(或喷针)机构,以减小水轮机原动能或者降低进水压力。

十二、项目:气体保护动作(瓦斯保护)过程:

气体保护动作的原因可能是:变压器内有轻微程度的故障,产生微弱的气体;空气侵入了变压器内。油位降低;二次回路故障(如发生直流系统两点接地等)引起误动作。

总结:

气体保护信号出现后,运行人员应立即对变压器进行外部检查。首先,应检查油枕中的油位和油色,气体继电器中有无气体,气体量与颜色等;然后,检查变压器本体及强油循环系统中是否有漏油现象;同时,查看变压器的负荷,温度和声音的变化,经外部检查,为发现任何异常现象时,报告修理人员,并吸取变压器的瓦斯气体,查明气体的性质,必要时要取其油样进行化验以共同判明故障的性质。

十三、项目:油开关拒绝跳闸的故障分析 过程:

油开关拒绝跳闸的原因有:(1)操作回路断线或熔断器熔断;(2)失去操作电源或电压不足;(3)传动机构失灵;(4)辅助接点接触不良; 总结:

在操作室操作油开关,实行远程操作。设同期点的油开关,必须先进行同期操作或检查。操作时,应注意油开关位置指示灯-红、绿灯指示之正确性。油开关拒绝跳闸,应手动跳开油开关。找修理工查明原因,消除故障,为下次合闸做好准备。操作完毕后,应巡视检查。由于,隔离开关不能带负荷操作。为此,应与油开关操作配合,即合油开关前,应先合隔离开关,油开关跳闸后,才能拉开隔离开关。

十四、项目:调速器油泵不打油 过程:

如果调速器在运行中油泵不打油;首先,将调速器由自动切为手动检查厂用电和油泵电机的三相电源是否正常,检查继电器是否卡死,找修理工,汇报领导。总结:

在运行中我们要认证检查调速器油气比是否正常,调速器油泵电机是否有发热现象,是否有异味。厂用电三相电源是否正常,不要等到油压到16kg以下才处理,及时发现情况及时处理。

十五、项目:运行巡视电气设备危险点的分析 过程:

雷雨天气,大雾天气,夜间,大风天气,高温天气的危险点及控制措施。

总结: 1雷雨天气

(1)避雷针落雷,反击伤人;应穿试验合格的绝缘装备远离避雷针5米;

(2)避雷器爆炸伤人;应带好安全帽,不得靠近避雷器检查动作值。

(3)室外端子箱,瓦斯继电器进雨水;端子箱机构箱关关紧,瓦斯防雨罩完好。

2、雾天

(1)突发性设备污闪(雾闪)接地伤人;应穿绝缘鞋巡视。

(2)空气绝缘水平降低,易发生放电;在室外,不知措施或巡视时,严禁扬手;

(3)能见度低误入费安全区域内;巡视时要谨慎小心,认清位置。

3、夜间

(1)夜间能见度低易伤人;电筒照明电源合格,路灯完好,两人同时进行,相互关照。

(2)巡视路线不平整,易摔跤;认真检查,无窜动,保证行走安全。

4、大风天气

(1)外物短路;认真巡视,对外物及时处理;(2)准备防雨帽;

5、高温天气

(1)充油设备油位过高,内压增大,造成喷油严重渗油;认真监视油位变化,必要时请求停电调整油位。

(2)液压机构油压异常时,开关不能安全可靠动作;监视不超过极限压力,人工安全泄压,及时更换密封圈,建立专用记录进行监视分析。

十六、项目:机组轴承(导轴承)故障分析 过程:

导轴承主要承受主轴传来的径向力,其作用主要是限位,防止机组在运行时产生旋轴摆动,承受主轴传来的径向负荷。其主要由轴颈,轴瓦,托板,调整螺钉,轴承体,油槽,轴承盖板,冷却器,挡油管,观察窗,油槽密封,油颈密封等部件组成。

总结:

导轴承主要故障:

(1)轴颈与轴瓦间隙增大,转子机械不平衡转子电气不平衡;制造缺陷,支座振动增加,机组支座上的交变力、螺纹或垫削弱或挤压。间隙增大会导致主轴摆动增加,油膜破坏,摩擦面接触,瓦温升高瓦磨损面熔化损坏。

(2)轴承结构缺油循环不良;(3)轴颈与轴瓦间的润滑油流量过大过小;(4)发电机转子间隙产生不均匀;

(5)轴承电流绝缘被导电的沉积物覆盖,绝缘机械性破坏,检温计外层金属线接地导致电流通过轴承摩擦部分,引起轴承摩擦表面的电腐蚀损坏使瓦面上出现磨痕,轴瓦钨金的表面熔化

(6)其他:润滑油标号不符,润滑油变质,刮瓦质量差,冷却器部分受堵,冷却器容量不够。

十七、项目:高油压数字阀式可编程调速器关于耗油量过大的处理方法

总结:

可按顺序排查并采取相应解决措施(1)管路连接有松动产生泄露;(2)蓄能器内氮气不足;(3)安全阀调值不正确;(4)油泵出口单向阀密封不良;(5)截止阀泄露;

(6)液压缺串腔另外,若油口混入空气,将引起液压缸动作迟缓,反应滞后处理方法是反复操作液压缸往复全行程排除空气即可。

十九、项目:GYT-600K型高油压数字阀式可编程调速器的正常运行

过程:

GYT-600K型调速器为单电机,油泵加手动泵,一个蓄能器运行方式有:手动运行包括手动停开机手动增减负荷及手动带负荷运行。自动运行以及手动、自动工况的相应切换以及事故停机。

总结:

调速器采用220V供电,电交流、直流互为备用,一种电源消失不会影响调速器的正常运行。但如果厂用直流消失,调速器将不能进行紧急停机(现在用直流供电)调速器处于手动状态时,手动指示灯亮;调速器处于自动状态时自动指示灯亮。手动和自动可以相互随时无条件的进行切换。一般自动运行在操作时特别要注意检查在自动还是手动运行。带压负荷用手动给减,给增开关进行操作运行时如果想切换画面进行超标是只需轻轻触摸屏幕任意位置,屏幕自动显示。

二十、项目:主变冷却风扇的运行分析 总结:

风扇平时在自动运行,如果温度升高,风扇不运行。风扇是靠电接点温度计启动,电接点温度计频繁启动,触电易老化,所以要将自动运行切换为手动运行。

冷却风扇在运行中应注意事项:

(1)检查信号继电器,中间断路器等是否良好;(2)检查三相电源是否有缺相现象;(3)检查风扇启动运行时是否有异常响声;(4)手自动切换是在故障是切换

二十一、项目:隔离刀闸操作基本要求的分析 总结:

严禁隔离刀闸带负荷操作,操作是要与断路器配合,三相联动的隔离刀闸,开合应同时进行,且3相差距不应大于3mm,三相单联刀闸的操作(拉开开关时,应先拉开中间相,在拉开其他两相,合上开关时,先合上左右两相,再合上中间相。隔离刀闸操作时要按原则进行,合上开关时,开始要慢,快接近时迅速合上,防止发生弧光,如已产生弧光,应迅速合上禁止再往回拉,终了时要慢,遵循慢-快-慢原则。拉时应慢且谨慎,当动静触头刚离开时,发生弧光应立即合上,重新检查断路器是否已真正断开,如果是切断小负荷电流(电压互感器、空载、用变等)设备室将会有电弧产生,这就应该迅速将隔离开关拉断开,当终了时要慢,防止回转时过程。

二十二、项目:联络开关并网运行分析 总结:

并网必须满足电压相等、相位相同、相序一致、频率相等,当这些条件都满足时,操作者只有在相角差最小时才能操作。

过程:

发电机的同步并列,应满足电压相同,频率相同,相位相同三个条件。如果由于个人操作不当,发电机就会非同期并列,并列合闸瞬间将产生巨大的电流冲击,是机组发生强烈的振动发出鸣音,发电机本体由于冲击力矩的作用而发出“吼”的声音,定子电流表、电压表摆动。

总结:

发电机非同期并列时,危害很大,它对发电机及其变压器断路器等电气设备破坏极大,严重时会将发电机绕组烧坏。发电机非同期并列时,我们应根据事故现象进行迅速而正确地处理。并列后,若机组产生很大的冲击或引起强烈的振动电流,电压表摆动剧烈而且不衰减。应立即断开机组开关和灭磁开关停机,待转动停止后,测量定子绕组绝缘电阻,确无问题后方可再次启动机组。

二十三、项目:混流式水轮机导叶剪断的运行分析 过程:

对导叶剪断做了一下几点分析(1)剪断销剪断一般原因(2)剪断销的作用

(3)导叶剪断销剪断出现的状况和处理过程 总结:

运行中发现剪断销剪断时,中控水机、故障信号灯亮,警铃响上位机剪断光字牌亮,机组振动摆度增大。运行人员首先检查剪断销剪断数目,调速器切手动调整机组负荷。使机组脱离振动区联系检修处理。

第四篇:发电厂电气运行考核制度

泰钢发电厂电气运行专业考核制度

一、总则

为了保证生产,保证发电厂设备安全稳定经济运行,工人认真负责,实事求是,不弄虚作假,不隐瞒事故、故障及其他错误,提高工人素质及技术业务水平,让工人知道应做什么,不应做什么,把应做的工作和事情落实到实处,规范工人在生产中的行为,加强安全生产的运行管理,特别制订本考核制度。

二、考核的具体规定

(一)接班时违反规定制度的处罚标准

1、全体电气运行人员必须按规定的顺序进行工作,不准未经批准和私自调换值班时间,违者,每次处罚5-10元。

2、接班人员必须在正点前20分钟换好工作服,并到达值班现场办理交接班手续。

① 没按时间到达现场或未换好工作服者,每次罚款5元。迟到者按公司规定进行处罚。

② 未办理交接手续,或手续不全,交接不清,不签字或不按规定顺序交接签字者,每次罚当班班长10元,当事人罚款5元。

③ 接班班长不开班前会,每次罚班长10元。

④ 接班时,要把应交接的各种工具、安全用具、备品等清点数目,检查好坏,并进行整理,放在固定地点位置,摆设整齐,违反者罚款5元。

⑤ 接班人员应查阅表单和各种记录,详细了解前值情况。此项工作不做或不了解情况者,罚款5元。

(二)交班时违反规定制度的处罚标准

① 交班人员必须将班中情况向接班人员交代清楚,不得敷衍了事,按规定顺序签字,违者罚款10元。

② 交班班长不开班后总结会,每次考核班长10元。

③ 交班前做好岗位卫生和责任区卫生。清扫用具及有关物品要进行整理,放置固定位置,并存放整齐,违反者罚款5元。

④ 工具、安全用具备品等要对口交接,数目核实清楚,并完好无坏损,违反者罚款5元。

⑤ 交班人员在交接完后,由班长带领统一离岗,不得私自或单独离岗,违者罚款10元。

(三)违反巡回检查制度的处罚标准

值班人员要按规定对设备进行巡回检查。

① 不按规定时间进行巡检者,罚款10元。

② 不按规定路线、时间,对设备进行逐个检查,有漏项者,罚款10元。③ 巡检时不遵守安全工作规程安全要求者,罚款10元。

④ 设备有缺陷不能及时发现者,罚款30元。

⑤ 巡检外出和巡检返回及巡检结果要向班长报告,并作好巡检记录,违者罚款10元。

(四)违反监盘制度的处罚标准

① 监盘期间,必须精力集中,不做与监盘无关的事,违者罚款10元。② 监盘坐姿要端正,不说闲话,不磕头打盹,不在电话中纠缠。违者

罚款5元。

③ 监盘应对各信号、参数清楚,掌握运行状态,及时调整有关参数。

违者罚款10元。

(五)两票、表单、各种记录管理处罚标准

1.工作票和操作票是保证安全生产的重要措施,加强两票管理是一项重要

工作,不得出现差错。

(1)操作票有下列差错之一者,每项罚款5元。

① 操作任务填写不明确;

② 操作票内关键字写错;

③ 操作票顺序颠倒、中间缺项或插项等;

④ 一个操作顺序格内填写两个以上项目;

⑤ 操作中的重要安全项目,如检查开关、刀闸的位置;

⑥ 操作票任意涂改且班长未盖章;

⑦ 操作票使用不严肃,任何一人未签字或代签;

⑧ 一个操作任务的操作票有两页以上者,未在前一页末未盖“转下

页”和后下一页前未盖“接上页”章者;

⑨ 操作票忘写开始和终结时间者;

⑩ 执行完的操作项目未打“√”者;

⑪ 执行操作票时不唱票,不打“√”,未严格执行监护制度;

⑫ 操作中不正确使用安全用具或不使用安全用具;

⑬ 不正确使用标识牌;

⑭ 执行完的操作票未盖“已执行”章或盖章不严肃;

⑮ 工作票不按编号使用或撕页;

⑯ 操作完后,各种记录应记录而未记录或记错。

(2)在工作票执行中有下列之一差错者,每项罚款5元。

① 已拉开开关及刀闸栏内填写不全,或两张填的不一样;

② 带电部位填写不够明确或写错;

③ 不去现场发票和核对安全措施;

④ 不去现场收票和不验收检修情况;

⑤ 工作票发出值长未签字;

⑥ 工作票发出或终结时间写错,或两张不一样;

⑦ 工作票发出或终结签字不全,或签错位置;

⑧ 工作票签字登记本上时间记错或人员记错;

⑨ 一个工作负责人手中发出两张工作票;

⑩ 在同一电气设备上同时发出检修票和实验票;

⑪ 新收到的工作票有错误未发现。

2.值班所抄表单是分析设备状况和生产管理的主要依据,所以报表表单的抄写一定要认真仔。

① 表单的抄写一定要用仿宋体,数字和文字一定要工整,排列美观。

凡不符合要求者,每次考核5元;

② 不得在表单表面和背面乱写乱画,如发现乱写乱画者,考核副值

5元,班长10元。

③ 表单上的签字一定要抄表本人签字,代签名或不签名者,罚款5

元。

④ 如表单损坏,破损或丢失考核当班者20元;

3.各种记录日志,记录簿要求。

各种记录日志,记录簿一定要认真记录填写,字迹要工整认真,按

要求签名。不得乱写乱画、缺页、损坏、破损、丢失。

发现有违者,按各项,每项次10元处罚。

(六)班中劳动纪律要求。

在班中要积极认真做好自己负责的工作,不得干与工作无关的事情。

1.不得在班中玩手机---上网或游戏,违反者每次罚本人30元,班长连带30元。

2.不得上班时间睡岗、脱岗,违者罚30元,班长连带30元。

3.各种物品、用具要按规定位置放置,各种记录、报表也应放置在指定位置,且标识清楚,违者罚款5元。

4.接到领导的临时任务或技术培训,不按时到达,考核10元。无故不来考核50元。

以上个各条款望电气运行人员认真执行,班长要监督执行,管理好本班人员,处理好各项事务。没有注明连带班长的,要根据情况不同程度的连带班长责任罚款。

违反劳动纪律和公司及厂规制度的,按公司和厂有关规定处罚执行。

电气运行专业

2012.12.

第五篇:发电厂电气运行管理制度

电气车间

运行管理制度汇编

二0一三年十二月十二日

(试行)

目录

1.岗位责任制 ··············································································································································· 1 1.1

车间主任职责 ············································································································································ 1 1.2

电气岗位责任制 ········································································································································ 1 1.2.1 班长的职责 ··············································································································································· 1 1.2.2 主值班员的职责 ······································································································································· 3 1.2.3 副值班员及厂用电工的职责 ··················································································································· 3 1.2.4 检修班长的职责 ······································································································································· 4 1.2.5 检修主修的职责 ······································································································································· 5 1.2.6 检修副修的职责 ······································································································································· 5 2.巡回检查制度 ············································································································································ 4 2.1

巡回检查管理的一般要求 ························································································································ 4 2.2

巡回检查时间 ············································································································································ 6 3.交接班制度 ················································································································································ 8 4.电气操作票、工作票管理制度 ·············································································································· 10 5.文明生产管理制度 ·································································································································· 14 6.设备缺陷管理制度 ·································································································································· 16 附录一:

操作票编号规定 ···························································································································· 18 附录二:

工作票编号规定 ···························································································································· 18

1.岗位责任制 1.1 车间主任职责

1.1.1 进行安全思想教育,使各级运行人员牢固树立安全第一的思想,及时表扬好人好事,推动班组和岗位的评比竞赛,加强班组建设。

1.1.2 负责领导本专业运行人员的培训及规程制度的学习和考试;针对季节性特点和运行工作的薄弱环节,研究部署特殊培训,安排好安全学习日的学习计划,组织反事故演习,提高学习效果。

1.1.3 每日进行现场巡视,查阅运行日志及各项记录,督促检查运行人员贯彻项执行各项规程、制度,定期参加交接班,检查清洁卫生工作。

1.1.4 分析设备技术状况和不安全现象,定期召开班组长会议,研究部署安全检查,反事故演习,分析异常运行和误操作情况,分析经济指标完成情况,制订对策和措施。1.1.5 现场监护复杂操作及系统操作,主持本专业主机及重要辅机检修后的验收启动和运行试验。

1.1.6 批准本专业系统图。

1.2

电气岗位责任制 1.2.1 班长的职责

1.2.1.1 班长是本班生产和行政上的负责人,在值班时间内,对电气全部设备的安全经济运行负责;领导全班完成上级交给的一切工作任务;班长在行政上受车间主任领导,在运行操作上受值长的领导和指挥。

1.2.1.2 班长应熟知发电厂一次系统、厂用电系统、直流系统、继电保护、自动装置及各种运行方式、掌握发电厂各类电气设备结构、特性、操作维护。

1.2.1.3 班长在值班时间内,负责与调度的联系工作;负责领导本班全体人员完成电气设备的安全、经济运行任务,为此应做好以下工作:

1.2.1.3.1 及时与调度联系并接受调度命令,并及时将调度令汇报值长。

1.2.1.3.2 领导全班人员做好交接班工作;带头执行规章制度,严格值班纪律,并检查全班人员的执行情况。

1.2.1.3.3 负责领导全班人员对电气设备的事故及异常运行进行正确迅速的处理,并对事故的发生及处理经过做好记录和分析。

1.2.1.3.4 注意完成本班计划指标,保证电能质量,随时分析运行情况,督促指导监盘人员精心调整,及时向值长提出必要的意见和要求。

1.2.1.3.5 认真做好运行设备缺陷管理工作,重大紧急缺陷及时报告上级领导。1.2.1.3.6 按时认真、详细地查阅、填写各种运行和技术记录。1.2.1.3.7 负责审查并监督做好第一、二种工作票的安全措施。1.2.1.3.8 担任第一、二种工作票和低压操作票的许可人。1.2.1.3.9 批准、审查操作票,担任高压设备操作的监护人。1.2.1.3.10 接受值长下达的停、送电操作命令。1.2.1.3.11 发布低压电气设备停、送电操作命令。

1.2.1.3.12 抓好班内安全技术培训和图纸、资料管理及清洁卫生工作。1.2.1.3.13 亲自担任监盘工作,每班不得少于2小时。

1.2.1.4 班长参加值长召开的运行分析会,负责贯彻分析会上研究决定的事项。1.2.1.5 班长根据领导的安排,领导学习活动,负责对值班员的技术业务指导工作。1.2.1.6 班长应掌握全班人员的思想情况,做好政治思想工作。

1.2.1.7 当班长不在时,代理班长不得离开控制室,并根据调度员和值长的要求进行联系,这些联系工作事后必须向班长汇报。

1.2.2 主值班员的职责

1.2.2.1 主值班员是厂用电气设备安全、经济运行的负责人,主值班员应熟知发电厂主接线系统、直流系统、厂用电系统、照明系统及主要电气设备运行特性、极限参数、继电保护、自动装置、厂用系统二次接线、额定数据、动力保险定值等。

1.2.2.2 主值班员在运行操作和行政关系上受班长的领导,并协助班长搞好本班培训及其他管理工作。当班长离开控制室时,主值班员应代替班长的职务。

1.2.2.3 主值班员的主要工作岗位是控制室,主要职责是监盘,合理地调整机组有、无功负荷,保证机组安全、经济运行和电能质量,并能正确使用信号,每班监盘一般不小于4小时。在班长的统一指挥下,主动、迅速、正确地处理事故及异常运行。在事故和异常运行情况下,应由班长监盘。

1.2.3.8 在班长的监护下进行电气设备的倒闸操作,填写倒闸操作票。

1.2.2.4 负责厂用电系统、直流系统、照明系统的检查、维护及停、送电操作,在班长的监护下进行厂用系统的倒闸操作。

1.2.2.5 根据班长的指示做好厂用电系统工作票的安全措施。

1.2.2.6 在班长的统一指挥下,主动、迅速、正确地处理事故和异常情况。1.2.2.7 根据值长的指示,主值班员可以担任厂用系统工作票的许可人。

1.2.2.8 对机、炉人员不符合电气设备规定的操作和不合理的运行方式,提出建议,并给予适当的纠正。

1.2.3 副值班员及值班电工的职责

1.2.3.1 副值班员及值班电工在行政上受班长领导,在运行操作及业务技术上受班长和主值班员的指导。

1.2.3.2 副值班员及值班电工应熟知主接线系统、厂用电系统、直流系统及发电机变 3

压器等主要电气设备的极限电流、温度及其他主要极限参数。

1.2.3.3 当主值班员不在时,副值班员及值班电工应主动代替主值班员的工作。1.2.3.4 搞好报表、仪表、安全用具、钥匙及材料备品的管理工作。1.2.3.5 按时正确地记录报表及电量计算。

1.2.3.6 负责监视发电机、主变压器、厂用变压器的温度变化。1.2.3.7 负责发电机滑环清理及碳刷维护和更换工作。1.2.3.8 在监护下,做好工作票的安全措施。

1.2.3.9 协助主值班员做好监盘工作,每班不少于1小时。

1.2.3.10 发生事故和异常时,在班长的统一指挥下,协助处理事故,根据班长的命令复归保护装置,详细、准确地做好保护动作情况记录。

1.2.4 检修班长岗位职责

1.2.4.1 检修班长在车间主任的领导下,对班组的各项工作全面负责。1.2.4.2 检修班长是班组安全生产第一责任人,对本班安全生产负责。1.2.4.3 推广应用现代化管理方法和手段,提高班组管理水平。1.2.4.4 搞好设备检修全面质量管理,保证设备保持较高的健康水平。1.2.4.5 根据本厂下达的年、季、月工作计划,制定出本班的工作计划。1.2.4.6 负责班组的经济责任制考查考核工作。

1.2.4.7 根据上级安排,积极无条件地配合各运行班组完成任务。1.2.4.8 坚持“安全第一、预防为主”的方针,努力实现三不伤害。1.2.4.9 坚持定期巡回检查和每天查看缺陷的制度,及时组织消缺。1.2.4.10 严格工艺作风,严把质量关,搞好设备检修记录及各级验收工作。1.2.4.11 搞好备品备件、劳动工时定额和物质消耗定额,使班组生产工作计划定额化、程序化。

1.2.4.12 负责监督、指导设备检修工艺、进度和质量及原始记录的准确和齐全。

1.2.5 检修主修岗位职责

1.2.5.1 主修工接受本班班长的领导,负责分工范围内的工作,确保检修质量。1.2.5.1 制定设备检修的技术措施,做好修前准备。

1.2.5.1 指导班组人员进行试验,并做好试验记录,分析试验结果,得出正确的结论。1.2.5.1 严格执行检修工艺规程和质量工序管理卡,严把质量关,搞好验收工作。1.2.5.1 检修工作结束做好设备检修记录。

1.2.5.1 对运行中异常进行分析判断,找出故障原因,提出消除故障的技术措施。1.2.5.1 对自己所管辖的设备负安全运行及保证健康水平的责任。

1.2.5.1 对班长安排的各项生产及非生产作业任务,负有全面贯彻执行的责任。1.2.5.1 对设备的安全运行、预防和消灭各种事故、障碍、异常、缺陷和减少设备临修,负有直接责任。

1.2.5.1 坚持设备卫生清扫制度,检修工对自己分管的设备进行卫生清扫及检查。对发现的设备缺陷,需要进行的检修改进更换的零件心中有数,并及时汇报班长.按消除设备缺陷的程序及时进行登记,待班长安排消缺。

1.2.5.1 主修工应在申请批准时间内,保证检修质量,完成工作票所规定的工作内容,千方百计地消除缺陷,对因某些客观原因造成的不能按时完成工作任务,应及时汇报,办理延期手续。

1.2.5.1 对于消除缺陷设备投用后,应及时了解设备运行情况及缺陷消除情况。1.2.5.1 按计划工期,在班长统一安排下,按时完成分配的各项任务。

1.2.6 检修副修岗位职责

1.2.6.1 副修工接受本班班长和主修的领导,负责分工范围内的工作,确保检修质量。

1.2.6.1 对自己所管辖的设备负安全运行及保证健康水平的责任。

1.2.6.1 坚持设备卫生清扫制度,检修工对自己分管的设备进行卫生清扫及检查。对发现的设备缺陷,需要进行的检修改进更换的零件心中有数,并及时汇报班长.按消除设备缺陷的程序及时进行登记,待班长安排消缺。

1.2.6.1 对班长或主修工安排的各项生产及非生产作业任务,负有全面贯彻执行的责任。

1.2.6.1 副修工应在消除设备缺陷后,将现场清理干净,做到现场无杂物,设备完整,地面清洁,最后工作负责人方可办理工作票结束工作,运行人员验收合格终结此项工作。

1.2.6.1 接受班长分配的班组安排的各种临时生产工作任务。

1.2.6.1 副修在接受班长分配的临时工作任务后,应积极主动保证质量,按照要求的工期完成任务,遇到的问题及时向班长汇报。如遇到特殊情况,任务不能按期完成,应报告班长进行调整和延期。

1.2.6.1 对设备的检修工艺、进度和质量做好完整的记录。

1.2.6.1 副修工接到班长或主修工分配的消缺任务后,应由工作负责人写出合格的检修工作票,按正常程序进行申批,同时做好工器具的准备工作。

2.巡回检查制度

2.1 巡回检查管理的一般要求:

2.1.1 为加强对设备的监视,及时了解和掌握设备运行情况,发现和消除事故隐患,保证设备正常运行,运行各岗位值班人员应严格执行本制度。2.1.2 值班人员应按规定的检查路线和检查项目进行认真检查。

2.1.3 巡回检查工作应由岗位值班人员或经考核合格正在实习的值班人员负责进行,6

在巡回检查中不应从事与检查无关的事情。

2.1.4 各岗位值班人员在巡回检查时思想要集中,应根据检查标准和设备实际情况进行认真分析,确保巡回检查质量。

2.1.5 检查时应携带所需工具,包括:听音棒、手电筒、测温仪、抹布等;做到:腿要走到、眼要看到、耳要听到、鼻要闻到、手要摸到。

2.1.6 检查人员应根据部颁《电业安全工作规程》和厂颁《运行规程》的要求进行巡回检查,戴好安全帽,必要时应穿绝缘鞋和戴防高温手套,注意自我保护,确保巡检安全。

2.1.7 当遇有雷、雨、大风、洪水、高温、严寒等恶劣天气,除进行正常巡回检查外,应加强重点检查。

2.1.8 遇有运行方式变更、设备运行异常、设备过负荷或带病运行、备用设备故障或正在检修、新设备试运行等,应有目的的增加巡回检查次数,做到心中有数。2.1.9 巡回检查过程中发现的异常情况,应根据设备异常类别及时处理,如本班不能消除,应汇报值长,并尽可能采取措施防止缺陷扩大;对于危及人身及设备安全的紧急情况来不及汇报时,应根据运行规程的规定先处理后汇报。

2.1.10 对于无故不进行巡回检查、玩忽职守,造成事态扩大者,分场将给予责任人严厉考核。

2.1.11 对巡回检查不认真、不能及时发现设备缺陷而导致缺陷扩大或缺陷由上一级部门检查发现者,将视情况在三工转换中考核。

2.1.12 各岗位应按下列时间进行巡回检查,遇有异常情况或重大操作,可经值长确定同意推迟检查时间或取消一次检查。

2.2 巡回检查时间 2.2.1 班长巡回检查时间

除交接班检查外每班次要对所属设备、公用系统等进行一次全面、认真检查。2.2.2 电气主值巡回检查时间

除交接班检查外每班次要对设备进行两次全面,认真检查。2.2.3 电气副值、厂用电工巡回检查时间

除交接班检查外每班次根据巡回检查卡对设备进行全面检查。2.2.4 检修主修、副修巡回检查时间

每班至少对运转辅机设备全面检查两次,值夜班检修人员至少对运转辅机设备全面检查一次。

3.交接班制度

3.1 全体值班人员必须严格执行集体交接班制度;按规定的运行人员值班表进行值班,未经班长批准不得调换值班班次。

3.2 交接班以GPRS时钟为准,正常情况下应正点交接班,不得无故拖延并由交接双方共同签字。

3.3 在事故处理或重大操作中不得进行交接班,只有在操作或事故处理告一段落并得到值长的许可后方可进行交接班。如果交接班的签字尚未完成时发生事故,由交班人员负责处理,接班人员在交班班长的指挥下协助处理。

3.4 因病或有事不能上班者,应在接班前四小时向班长请假,请假手续由自己办理,不得由他人代办,批准后方可休息。

3.5 严禁酒后上班,如发现酒后上班者,班长应令其退出现场,安排人替班并及时汇报车间主任。

3.6 若接班人员未按时接班或有酒味,精神不振等现象,交班人员应报告班长并继续值班,不应擅离岗位,待有人来时方离开岗位,但连续值班不得超过11时,班长应尽 8

快安排人员值班。

3.7 交班人员应虚心听取接班人员提出的批评意见;并做到认真解答提出的问题。3.8 交接班应做到交得清,接得明,因交接班不清造成的后果由交班人员负责。3.9 交班人员应做到以下几项:

3.9.1 交班前两小时按分管的设备专责进行卫生清扫工作。

3.9.2 交班前一小时按分管的设备专责进行全面检查,整理好值班和一切技术记录,整理好工具,仪表,备品备件,安全用具等。3.9.3 向接班人员详细介绍交待:

──设备及系统运行方式、本班和前班进行的变更操作;── 定期工作的完成情况,设备系统所做的试验及有关数据;──发现的设备缺陷及发展情况,为预防事故所采取的措施、异常现象的处理经过和分析情况;──保护及自动装置的运行及变化情况

──工作票情况,设备检修情况及新布置的安全措施;──预计下班进行的工作和操作;──本班和前一班的工作中取得的经验、发生问题及教训;──上级命令及执行情况;3.9.4 接班人员正式到达岗位后进行交班手续,待接班人员在值班记录簿上签字后方可离开现场。

3.9.5 交班前半小时召开班后会,班长总结当班工作。3.9.6 若本班发生异常情况由班长负责组织分析。3.9.7 接班人员应做到以下几项:

3.9.7.1 接班人员应在接班前20分钟到现场,听取交班班长的口头交待,并认真查看值班和其他一切记录。

3.9.7.2 听取交待后,各岗位接班人员按各自的职责和分工,对所辖设备进行详细检查。

3.9.7.3 接班人员检查完设备后了,听取本岗位交班人员的交待,若发现设备系统运行状况及参数与交待情况不符,应向交班者了解清楚,并要求符合规定和做好记录。3.9.7.4 检查所辖区域的卫生情况及消防器材,若发现卫生不符合要求,消防器材不全或移动位置,应向交班者提出,交班者应即清扫或处理,否则不予接班。3.9.7.5 交班前5分钟参加接班碰头会,向班长汇报检查情况及所发现的问题,听取班长的工作布置,安全注意事项、事故预想等,全体人员做到正点签字交接班。3.9.7.6 接班后,接班班长向值长汇报(电话汇报或当面汇报)接班情况,并听取其指示。

3.9.8 以下情况不应交接班,待问题处理好后,经领导批准后方可交接班。3.9.8.1 本岗位人员未到不交接。

3.9.8.2 运行设备发生异常,原因不明不交接。3.9.8.3 运行方式不清楚,记录不完整不交接。3.9.8.4 重大操作或事故处理未完毕不交接。3.9.8.5 各项定期试验未完成不交接。3.9.8.6 设备、环境不干净不交接。3.9.8.7 公用工具不明不交接。

3.9.8.8 接班人员酒后或精神不振不交接。

4.电气操作票、工作票管理制度

4.1 操作票、工作票及停送电联系单,必须严格执行部颁«电业工作规程»(发电厂及 10

变电所部分)中的有关规定。4.2 下列操作应填写倒闸操作票:

4.2.1 6KV及以上的倒闸操作(包括拉合两组以上的接地刀闸)。4.2.2 厂用400V母线的停送电及厂用电源的倒闸操作。4.2.3 各厂用电源倒换及停送电操作。

4.3 下列操作不须填写操作票,可根据值长或电气班长的命令并经复诵无误后在监护下进行,但必须记入值班记录簿及相关记录簿中: 4.3.1 事故处理时。4.3.2 拉合开关的单一操作。

4.3.3 拉开接地刀闸或拆除全厂仅有的一组接地线。4.3.4 备用电源自投装置的投入与解除。4.3.5 重合闸解除或投入。

4.3.6 保护及自动装置的压板切换、投入或解除的单一操作。4.3.7 电动机摇测绝缘。4.3.8 开关传动试验。

4.4 电气工作票使用范围

4.4.1 电气第一种工作票的使用范围

──高压设备上工作需要全部停电或部分停电时;

──高压室内的二次接线和照明等回路的工作,需要将高压设备停电或做安全措施时。4.4.2 电气第二种工作票的使用范围 ──带电作业和在带电设备外壳上的工作;

──控制盘和低压配电盘、配电箱、电源干线上的工作; ──二次结线回路上的工作,无需将高压设备停电者;

──转动中的发电机、同期调相机的励磁回路或高压电动机转子电阻回路上的工作; ──非当值值班人中员用绝缘棒和电压互感器定相或用钳形电流表测量高压回路的电流。

4.5 班长在签发命令票时,必须向操作人交代注意事项。操作前操作人必须与设备所属班长联系得到许可后方可进行操作。

4.6 操作必须由两人进行,一人监护、一人操作,监护人和操作人由班长认为可以胜任的值班人员担任。

4.7 下列项目应填入操作票内: 4.7.1 应拉合的开关和刀闸。4.7.2 检查开关和刀闸的位置。4.7.3 检查负荷分配。

4.7.4 安装或拆除控制回路或电压互感器回路的保险。4.7.5 装拆接地线。4.7.6 检查接地线是否拆除。

4.7.7 保护及自动装置的投入或停用。4.7.8 检查模拟图。4.7.9 必要的检查项目等。4.8 有关联系的注意事项: 4.8.1 电话联系,要互报姓名。

4.8.2 有关操作的联系,必须重复正确无误后方可执行,执行后立即汇报。4.8.3 设备操作禁止用打手势方式进行联系。

4.8.4 联系内容应简练,不谈与联系无关的事。

4.8.5 谁操作(监护)谁负责与有关方面进行联系,不可代转联系。

4.8.6 对联系工作有疑问或以为可能危及人身及设备安全时,应及时弄清,方可继续执行。

4.9 操作前必须带齐安全工具和其他必用工具(包括照明用具)。养成执行操作票的良好习惯,并做好以下规定: 4.9.1 操作前要做好事故预想。4.9.2 操作中要做到:

一查:检查操作项目与实际设备编号是否相等; 二看:看清设备的实际位置; 三操作:三秒思考再操作。4.9.3 在下列情况做到不操作 ──任务不清不操作 ──目的不清不操作 ──项目不对不操作 ──涂改不清不操作 ──发生疑问不操作 ──联系不清不操作 ──不带安全工具不操作 ──没有事故预想不操作 ──监护人未发操作命令不操作

4.10 操作票、工作票的登记应做到字迹工整、清楚明白、不漏记、不漏项。上月未销的工作在下月登记簿上重新登记。

5.文明生产管理制度

5.1 文明生产是企业素质的综合反映,为了保证设备的安全经济运行,创造一个设备完好窗明几净环境,整洁、井然有序的工作环境,为了加强鑫源职工的内外形建设,特制定本制度。

5.2 全体运行人员都应遵照《能源部火力发电厂文明生产若干规定》(试行),厂颁各项制度,搞好文明生产。

5.3 凡进入生产现场的人员都应自觉遵守本制度的有关条款。

5.4 交接班室、控制室是运行人员工作场所,为保证安全生产,与工作无关人员严禁随意进入。

5.5 凡进入控制室的人员不应违反本规定中的有关条文,否则值班人员有权制止或令其离去。私自进入交接班室、控制室的,值班人员应令其离去并汇报有关领导。5.6 值班纪律

5.6.1 运行人员应按«交接班制度»的规定按时上、下班,不应迟到、早退。5.6.2 凡因故及各种法定假需要休班者,应按规定办理请假手续,经批准后方可休班,否则按旷工处理。

5.6.3 值班期间因有特殊情况需处理时,应经班长同意,并有人顶替岗位后,方可离开现场。

5.6.4 值班人员应自觉遵守厂规,说话和气、尊重他人、讲究卫生、文明礼貌,不得影响他人工作。

5.6.5 各项记录、日志,不应在其上乱写、乱画、乱撕,应注意保存。5.6.6 各工器具应按定置管理的规定存放整齐,不得随意放置。

5.6.7 值班监盘时应集中精力注意各表计指示及运行状况,准确的发现异常运行情况 14

并及时汇报处理,不应在监盘时看一切书报,做与监盘无关的一切事项。

5.6.8 运行人员进入现场应自觉遵守«安全工作规程»中有关工作人员服装的规定穿着工作服,佩带岗位标志,进入现场应戴安全帽。(控制室除外)5.7 请假规定

5.7.1 运行人员因故请假应在接班前四小时向班长提出书面式、口头式请假。5.7.3 不应找别人代替请假,否则视为违反请假制度。5.7.4 私人找人替班应在接班前四小时经班长同意。5.7.5 工作中因个人责任造成的各种事件由替班人员负责。5.8 运行人员监盘管理

5.8.1 所有监盘人员必须经过培训考试合格,经所属专业主管批准后方可独立监盘,按计划实习人员实习监盘时,应有合格人员监护,发生问题时由监护者负责。5.8.2 监盘时应面向表盘,全神贯注,掌握表计的变化,及时调整。5.8.3 监盘时要保证各项运行参数不超过正常变动范围。

5.8.4 监盘时不抄表、不考问、不演习、不打盹睡觉、不零食、不做与监盘无关的任何事情,若须离开表盘时,必须有专人代替。

5.8.5 监盘时对运行方式要做到心中有数,特别是进行倒换操作时必须精神集中,遇有气候异常时,对可能要发生的事故要有充分的思想准备,以便处理。

5.8.6 对仪表的变化要勤分析,发现异常现象应及时汇报,查明原因,正确判断处理,交班时要详细交待。5.9 清洁卫生管理

5.9.1 交接班时必须按清洁卫生制,认真检查设备和工作现场地面的清洁。5.9.2 各班组的卫生区划分,应在岗位责任制中明确规定。

5.9.3 设备检修完毕应保证设备及地面卫生,否则不办理工作终结手续。

5.9.4 检修人员清扫设备时,应保持设备及地面卫生。5.9.5 清扫卫生时,应遵守«安全工作规程»有关规定。

6.设备缺陷管理制度

6.1 为了提高对设备缺陷的管理,实现安全、经济、稳发、满发和可靠、稳定地供热,特制定本制度。做到及时发现,积极消除设备缺陷是全体运行人员、检修人员的工作职责,要做到小缺陷不过班,大缺陷不过天,保证运行设备始终处于可控、在控状态,一时消除不了的缺陷一定要做好相应的安全措施。6.2 设备缺陷分类

6.2.1 设备缺陷按其对电厂安全运行的影响程度为分三类:

6.2.1.1 一类缺陷:主要设备,主要辅助设备,控制、保护及自动装置,不立即处理将威胁人身及设备安全或造成扩大事故的缺陷。

6.2.1.2 二类缺陷:虽能坚持运行,但影响设备安全运行的缺陷。

6.2.1.3 三类缺陷:虽能长期安全运行,但影响经济运行和出力或影响设备美观和寿命的缺陷。

6.2.2 设备缺陷依其类别不同,按下列时间处理: 6.2.2.1 一类缺陷应当即时处理。

6.2.2.2 二类缺陷自发现之日起,不超过7天进行处理。

6.2.2.3 三类缺陷,按期不同情况分别列入月、季或检修计划中给予消除。

6.3 设备缺陷处理程序

6.3.1 运行人员发现的缺陷,应报告当班班长,由运行班长检查、核实后填入《设备缺陷记录》汇报值长或车间主任,并联系电气检修人员处理消缺。检修人员及其它人 16

员在巡视设备时发现的设备缺陷也应首先通知运行班长,然后由运行班长汇报值长或车间主任。

6.3.2 检修车间缺陷处理程序

6.3.2.1 接到运行班长(运行值长)通知的缺陷,检修班长应立即安排人员消缺。6.3.2.2 检修车间收到设备缺陷通知后,首先将内容填写于<设备检修记录薄>,对能处理的,根据规定办理工作票,尽快安排消缺,对需要停运主设备才能处理的,报运行班长和车间采取必要措施,防止缺陷扩大,并由运行班长报值长。

6.3.2.3 消缺结束后,检修负责人应在《设备缺陷记录》上签字,办理此项缺陷处理的终结手续。

6.3.2.5 检修人员消缺完毕,由运行班长进行验收,除作好记录外,应将验收时间及结论报值长。

附录一:

操作票编号规定

操作票编号规定

为规范操作票编号并利于统计管理,规定操作票编号形式为AABBCCDDD,不得随意编号、登记。其中字母AA表示专业: DQ表示电气。数字BBCCDDD表示操作票号,从月初001开始编号。如电气专业2010年6月份第5份操作票,编号即为DQ0406005。

附录二:

工作票编号规定

工作票编号规定

为规范工作票编号并利于统计管理,规定工作票编号形式为AABBCCDDD,不得随意编号、登记。其中数字AA表示票种:D1表示一种票、D2表示二种票;数字BBCCDDD表示工作票号,从月初001开始编号。如2010年6月份第5份工作票,编号即为D11006005,或D21006005。

下载发电厂运行状态(推荐)word格式文档
下载发电厂运行状态(推荐).doc
将本文档下载到自己电脑,方便修改和收藏,请勿使用迅雷等下载。
点此处下载文档

文档为doc格式


声明:本文内容由互联网用户自发贡献自行上传,本网站不拥有所有权,未作人工编辑处理,也不承担相关法律责任。如果您发现有涉嫌版权的内容,欢迎发送邮件至:645879355@qq.com 进行举报,并提供相关证据,工作人员会在5个工作日内联系你,一经查实,本站将立刻删除涉嫌侵权内容。

相关范文推荐

    ×××发电厂运行交接班制度

    ×××发电厂运行 交接班制度二01三年十二月一日1、总则 1.1交接班制度是确保发电厂连续不断安全经济运行的重要环节,所有运行人员必须严格执行。 1.2所有运行人员必须严格按照......

    发电厂运行实习报告

    发电厂运行实习报告 专业班级电气工程及其自动化 姓名 学号 电气工程系 2017.1 在老师的带领下,我们来到了胜利油田发电厂进行了发电厂运行实习。经理论知识与生产实践相......

    如何做好发电厂运行工作范文

    如何做好发电厂运行工作 一 、做好发电和检修服务工作。  两票三制的规范执行,保证可控和在控。加强三票三制管理,各类票单要形成标准,养 成良好的工作习惯。  提高执行力,规范......

    发电厂并网运行管理规定

    《发电厂并网运行管理规定》 [ 作者:佚名 转贴自:电监会 点击数:747 更新时间:2006-11-9 ]发电厂并网运行管理规定 (征求意见稿 ) 第一章 总则 第一条为适应电力体制改革的需要,促......

    发电厂锅炉运行考试复习题

    锅炉考试复习题 一、填空题:(每空1分) 1、检查汽包水位计应投入, 清楚,汽、水侧各门好用;正常水位线与高低水位标志正确;云母片清晰,防护罩齐全牢固,安全可靠,照明良好。 2、投入锅炉......

    发电厂继电保护及自动装置运行规程[范文]

    继电保护及自动装置运行规程 目录 1. 继电保护及自动装置总则 ............................................... 3 1.1 总则 .................................................

    发电厂运行技术员先进事迹演讲稿

    各位评委、朋友们: 当你夜晚漫步走在灯火辉煌的街头,领略着竹城迷人的城市夜景之时;当你坐在电视机旁,和家人其乐融融地欣赏着优美的电视节目之时;当你睡在有空调的家中,享受着丝......

    发电厂设备状态检修管理的必要性